From load current, conductor and transformer, get the breaker rating, trip characteristic, fault current at the panel and at the end of the circuit, and the interrupting rating you need.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Maximum three-phase and minimum line-to-ground fault versus distance from the panel, with the breaker instantaneous trip.
Design current must be below breaker rating, and breaker rating below cable ampacity.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
Under the NEC, the breaker must be at least 125% of the continuous load plus 100% of the noncontinuous load, and it must protect the conductor (240.4). Round up to the next standard size in 240.6(A).
The maximum current a bolted fault would draw at a point, set by the utility, the transformer and the conductors. NEC 110.24 requires it to be marked at service equipment, and breakers must be rated for it (110.9).
Motor branch circuits use NEC 430: the breaker protects against short circuit (up to 250% of FLC for inverse-time breakers) and a separate overload relay protects the motor.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.