Enter flows and temperatures of both fluids, the arrangement and the overall coefficient to get the heat duty, outlet temperature, LMTD, F factor, area and the payback when the heat is recovered.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Temperatures of both fluids along the area, by the ε-NTU method.
Cooling the hot fluid further recovers more heat, but the area grows fast near the limit.
Cash flow of the improvement: investment in year 0 and annual savings escalated at the rate entered, discounted at the MARR.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
Run the heat balance to get the duty and the missing temperature, compute the LMTD between the ends and divide: A = Q ÷ (U · F · LMTD). Use a fouled U, as TEMA recommends.
In shell-and-tube exchangers with more than one tube pass, flow is not pure counterflow. F corrects the LMTD; below 0.8 the design is poor and usually needs shells in series.
For estimates: water-water 140–260 Btu/(h·ft²·°F); condensing steam to water 260–700; oil-water 25–70; gas-gas 2–9. Confirm with the manufacturer or a detailed rating.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.