Enter fluid, flows, pressures and valve type to calculate Cv and Kv per IEC 60534-2-1 / ISA-75.01.01, check choked flow and see the selected valve’s travel at minimum, normal and maximum flow.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Characteristic curve of the selected valve with minimum, normal and maximum flow points. The recommended range is 20% to 80% travel.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
Cv is water flow in US gpm at 1 psi drop; Kv is water flow in m³/h at 1 bar. Cv = 1.156 × Kv.
In liquids, when pressure at the vena contracta falls below vapor pressure. Per IEC 60534, flow chokes when the drop exceeds FL² · (p1 − FF · pv). Incipient cavitation can start before that.
Size the valve to run between 20% and 80% travel from minimum to maximum flow. Too open loses control authority; too closed is unstable and erodes the trim.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.