Enter pump flow and cut-in and cut-out pressures to get the tank volume that limits motor starts and the right air precharge.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
With the chosen standard tank; the maximum occurs when demand is half of pump flow.
For the same cut-in pressure, widening the band to cut-out reduces the tank.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
Compute drawdown (pump flow times minimum cycle time, divided by 4) and divide by the acceptance factor from Boyle’s law using absolute precharge, cut-in and cut-out pressures.
About 2 psi (0.2 bar) below pump cut-in, measured with the tank empty of water. Low precharge wastes volume; too high and the pump starts without the tank helping.
A small tank, wrong precharge or a ruptured diaphragm reduces drawdown, and the pump cycles more than the motor can take.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.