Enter the cables by outside diameter to find the smallest conduit that holds them within the fill limit and whether the chosen cable tray is large enough, without forcing the pull or overheating the cables.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Same cables in each trade size of the chosen type. Green: within the limit; red: above it.
Standard widths at the usable depth entered (at most 6 in counts).
Take this page’s results to another calculator with the fields already filled in.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
NEC Chapter 9, Table 1 allows 53% for one cable, 31% for two and 40% for three or more conductors or cables.
A 1 in EMT has 0.864 in² inside. At 40% fill (0.346 in²), it holds 7 Cat 6 cables of 0.25 in OD (0.049 in² each). With 0.30 in Cat 6A, it holds 4.
Two cables side by side span almost the whole diameter and tend to jam during the pull, especially in bends. Three or more settle together more easily.
For control, signal and communications cables only, NEC 392.22(A)(3) and (4) allow 50% of the cross-section in ladder or ventilated trough tray and 40% in solid bottom tray, using at most 6 in of depth.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.