Insulation resistance (IEEE 43)

Enter the megohmmeter readings and the winding temperature to see whether the insulation of a motor or generator meets IEEE 43 and how it has evolved between inspections.

Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.

Check
Machine
Test

Leave the 30 s or 10 min reading at 0 if it was not taken. Test with the machine off, disconnected and grounded; after the test, keep the winding grounded for at least 4 times the voltage application time.

Inspection history (paste from Excel)

One row per test: date; 1-minute resistance in MΩ; winding temperature in page units; PI (optional). Each reading is corrected to 40 °C (104 °F) to show the trend.

See what was read
—1-minute resistance corrected to 40 °C
—

Test absorption curve

Measured resistance and resistance corrected to 40 °C during the test, with the recommended minimum. Log scales.

Tap the chart to see the values.

Trend of corrected resistance

History readings corrected to 40 °C, exponential trend line and recommended minimum.

Tap the chart to see the values.

Next step

Take this page’s results to another calculator with the fields already filled in.

The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.

Method, assumptions and references

Equations used

Correction to 40 °C: R40 = Kt · RT, Kt = 0.5^((40 − T) ÷ 10) (T in °C)
Polarization index: PI = R10min ÷ R1min; absorption ratio: DAR = R60s ÷ R30s
Minimum at 1 min and 40 °C (IEEE 43-2013, Table 3): kV + 1 MΩ; 100 MΩ; 5 MΩ. Minimum PI (Table 2): 1.5 class A; 2.0 classes B, F and H
Leakage current: I (µA) = V ÷ R (MΩ); trend: ln R40 = a + b · year, yearly change = e^b − 1

Assumptions and limits

  • Temperature correction by doubling every 10 °C is the IEEE 43 approximation and works best near 40 °C. To compare inspections, always test at a similar temperature and voltage.
  • With 1-minute resistance above 5000 MΩ (corrected), IEEE 43 notes that PI may not indicate insulation condition.
  • The absorption ratio is not part of IEEE 43; the ranges shown are field practice published by Megger.

Standards and technical documents

  • IEEE Std 43-2013: Recommended Practice for Testing Insulation Resistance of Electric Machinery
  • IEC 60034-27-4:2018: Rotating electrical machines — Measurement of insulation resistance and polarization index of winding insulation
  • ANSI/EASA AR100: Recommended Practice for the Repair of Rotating Electrical Apparatus
  • Megger: A Stitch in Time — The Complete Guide to Electrical Insulation Testing

U.S. regulations

  • NFPA 70E: Standard for Electrical Safety in the Workplace
  • NFPA 70B: Standard for Electrical Equipment Maintenance
  • OSHA 29 CFR 1910.333: selection and use of electrical work practices

Frequently asked questions

What is the minimum insulation resistance of a motor?

Per IEEE 43-2013, the 1-minute reading corrected to 40 °C (104 °F) should be at least 100 MΩ for modern form-wound windings and 5 MΩ for low-voltage random-wound motors. For older machines use kV + 1: 5.16 MΩ for a 4160 V motor.

Why correct the reading to 40 °C (104 °F)?

Because resistance halves for every 18 °F (10 °C) of warming. A motor reading 1800 MΩ at 86 °F equals 900 MΩ at 104 °F; without correction, readings taken on hot and cold days cannot be compared.

How do I calculate the polarization index?

Divide the 10-minute reading by the 1-minute reading. With 5200 MΩ and 1800 MΩ, PI is 2.9, above the 2.0 minimum for class F. A PI below 1 points to wet or contaminated insulation.

What megger voltage should I use?

Per IEEE 43 Table 1: 500 V for windings up to 1000 V; 500 to 1000 V up to 2500 V; 1000 to 2500 V up to 5000 V; 2500 to 5000 V up to 12 kV. A 4160 V motor is tested at 2500 V.