Steam trap loss calculator

Enter the number of traps, steam pressure, orifice size and your latest survey results to see how much steam escapes and what it costs per year. Compare it with the cost of a survey and replacement program.

Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.

Preliminary estimate
Steam traps
Survey findings
Costs and survey program

Up-front investment is replacing every failed trap found. Annual cost adds the survey and replacing new failures at the remaining rate.

Economic analysis
—Annual cost of steam lost through traps
—

Steam loss per failed-open trap by orifice size

Napier’s formula with the discharge factor entered, at three steam pressures.

Tap the chart to see the values.

Annual cost today and with the survey program

Steam lost through open and leaking traps, plus the annual program cost.

Tap the chart to see the values.

Next step

Take this page’s results to another calculator with the fields already filled in.

Project payback

Cash flow of the improvement: investment in year 0 and annual savings escalated at the rate entered, discounted at the MARR.

Tap the chart to see the values.

The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.

Method, assumptions and references

Equations used

Napier (DOE Steam Tip Sheet #1): W = 24.24 · P · D² [lb/h; P in psia; D in inches]
Loss: ṁ = W · (Nopen · fo + Nleak · fl); annual cost = ṁ · hours × steam cost
With program: loss × (remaining ÷ current failures) + N · (survey + remaining rate × replacement)

Assumptions and limits

  • Orifice under critical flow of saturated steam (downstream pressure below about 58% of absolute inlet pressure, the usual case discharging to an atmospheric return).
  • The discharge factor accounts for condensate passing with the steam and partial blockage; the true value depends on trap type and condensate load. Preliminary estimate: confirm with measurement or the survey report.
  • Steam cost should include fuel, water, treatment and boiler-house power; the steam cost calculator helps you get it.

Standards and technical documents

  • U.S. DOE, Steam Tip Sheet #1: Inspect and Repair Steam Traps (Napier’s equation)
  • U.S. DOE, Improving Steam System Performance: A Sourcebook for Industry
  • SEAI: Guidelines for claiming energy savings from steam trap replacement (Napier formula and 50% correction)
  • ISO 7841: Automatic steam traps — Determination of steam loss — Test methods
  • Spirax Sarco: The Steam and Condensate Loop (steam trapping and trap testing)

U.S. regulations

  • OSHA 29 CFR 1910.147: control of hazardous energy (lockout/tagout) before trap replacement
  • ASME B31.1 Power Piping and state boiler laws for steam lines
  • EPA 40 CFR Part 63 Subpart DDDDD: energy assessment of boiler systems, including steam distribution, at major sources

Frequently asked questions

How much steam does a failed-open trap lose?

By Napier’s formula, a 1/8 in orifice at 150 psig passes about 62 lb/h of steam through a clear orifice. With a 50% discharge factor that is about 31 lb/h; over 6,000 h a year, about 187,000 lb, roughly $1,900 at $10 per 1,000 lb.

What is a normal steam trap failure rate?

Without a survey program, audits find 15% to 30% of traps failed. With annual testing and replacement of failed units, the rate stays below 5%.

Is a trap failed closed also a loss?

It loses no steam, but condensate backs up in the equipment: heat transfer drops and water hammer and corrosion appear. The cost is in production and maintenance and is not counted as steam here.

Why use a discharge factor?

Napier’s formula assumes a fully open orifice passing only steam. In practice condensate passes too and the orifice may be partly blocked; savings verification guides use 50% to avoid overstating the gain.