Paste the lab titration curve or use the theoretical method to see how much chemical to feed, what flow the metering pump needs and what it costs each year to keep pH within the limits.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Wastewater pH versus reagent dose, in meq per liter of wastewater. Dashed lines: country discharge range and target pH.
What it costs to neutralize to each pH with the chemical and price entered. Aiming beyond what is needed raises cost.
Take this page’s results to another calculator with the fields already filled in.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
Titrate a 100 mL sample with 0.1 N caustic, recording pH. If pH 7.5 occurs at 9.33 mL, the dose is 9.33 × 0.1 ÷ 100 = 9.33 meq/L, or 373 g of NaOH per m³ (3.1 lb per 1,000 gal). For 100 gpm that is about 18.7 lb/h of pure NaOH, or about 900 lb/d of 50% caustic.
pH measures only free H⁺. Wastewater at pH 2.8 has 1.6 meq/L of free acidity, but weak acids, metal salts and buffers can call for 9 meq/L or more. The titration curve shows the real dose.
NPDES permits usually require 6.0 to 9.0. Discharges to a POTW below pH 5.0 are prohibited by 40 CFR 403.5(b)(2) unless the plant is designed for them, and local limits often apply; waste at pH 2 or below, or 12.5 or above, is RCRA corrosive.
Lime usually costs less per equivalent, but it makes more sludge, scales lines and reacts slowly. Caustic is clean and fast; at small flows the cost difference matters little.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.