List cameras, access points and phones with their class or power to see whether the switch can carry them, how much is lost in the cable and how big a UPS the setup needs.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Sum of all ports of each type: power delivered to the PD, cable loss and class reserve the switch locks without using.
Port delivering the class limit at the voltage entered, with the chosen cable. The gap to port power is the cable loss.
Values per port except the last column. Current per pair set.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
802.3af gives up to 15.4 W at the port and 12.95 W at the device; 802.3at (PoE+) 30 W and 25.5 W; 802.3bt Type 3 60 W and 51 W; Type 4 90 W and 71.3 W. The gap is the loss allowed over 100 m (328 ft) of cable.
It depends on current and length. A 25.5 W PoE+ port at 50 V over 328 ft of Cat6 (23 AWG) at 104 °F loses about 2 W. In the standard worst case (12.5 Ω per loop) the loss reaches 4.5 W.
It depends on configuration. With class-based allocation, a class 3 camera drawing 6.5 W locks 15.4 W of budget. With LLDP allocation the switch reserves only what the device requests, freeing power for more ports.
Add the real power delivered at the ports, divide by power supply efficiency (about 90%) and add the switch’s own draw. With 330 W of PoE and 60 W for the switch that is about 430 W, or a 600 to 1,000 VA UPS depending on runtime.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.
© 2026 Indus Metrics. Found an error? Write to contato@seudominio.com.