Enter protocol, baud rate, cable length and devices to see whether one segment is enough, how many repeaters and terminators to use and how long the Modbus master takes to poll every slave.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
RS-485 from the TIA-485-A practical curve (4,000 ft up to about 90 kbit/s, then L × rate ≤ 10⁸ m·bit/s); Profibus DP from the IEC 61158 table for type A cable.
Same network and messages at each rate. Past a certain point, slave response time dominates and a faster rate barely helps.
The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.
About 4,000 ft (1,200 m) per segment up to roughly 90 kbit/s. Above that, use the rule length × rate ≤ 10⁸ m·bit/s: at 115,200 bit/s, about 2,850 ft. With repeaters, each segment adds another 4,000 ft.
32 unit loads per segment. With 1/8 unit-load transceivers, 256 devices. Modbus allows 247 slave addresses; Profibus DP, 126 stations.
At 19,200 bit/s, reading 10 registers (8-byte request, 25-byte response) with a 10 ms slave response takes about 31 ms per slave, or 309 ms for 10 slaves.
200 m (656 ft) per segment with type A cable. At 12 Mbit/s it drops to 100 m (328 ft); up to 93.75 kbit/s it reaches 1,200 m (3,937 ft). Each segment takes 32 stations, including repeaters.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.