RTD (Pt100) and thermocouples

Pick the sensor and enter the temperature, or the measured signal, to get ohms or millivolts from the official tables, the class tolerance, the cold-junction effect and how much the cable errs with each connection.

Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.

Check
Sensor and conversion
RTD
——
—

Sensor curve over its range

Resistance (RTD) or emf with cold junction at 0 °C (thermocouple), with the computed point.

Tap the chart to see the values.

Sensor tolerance versus temperature

Maximum deviation allowed by the class, in ± degrees, within each class validity range.

Tap the chart to see the values.

Next step

Take this page’s results to another calculator with the fields already filled in.

The report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. In the print dialog, choose Save as PDF.

Method, assumptions and references

Equations used

Pt100/Pt1000: R(t) = R0 · [1 + A·t + B·t² + C·(t − 100)·t³]; A = 3.9083·10⁻³, B = −5.775·10⁻⁷, C = −4.183·10⁻¹² (C = 0 for t ≥ 0 °C)
Inverse for R ≥ R0: t = [−A + √(A² − 4B · (1 − R/R0))] ÷ (2B); below 0 °C, Newton-Raphson on the full equation
Lead error: 2-wire Δt = 2 · Rc ÷ (dR/dt); 3-wire Δt = δ · Rc ÷ (dR/dt); 4-wire Δt = 0; Rc = ρ · L ÷ A
Thermocouple: E(t) = Σ cᵢ · tⁱ (+ a0 · exp[a1 · (t − 126.9686)²] for type K above 0 °C); t = Σ dᵢ · Eⁱ (NIST inverse)
Cold junction: E(T) = E_measured + E(T_cj); error ≈ cold-junction sensor error × S(T_cj) ÷ S(T)

Assumptions and limits

  • Direct coefficients from NIST SRD 60 / Monograph 175 (same as IEC 60584-1) and inverses with a maximum error of 0.02 to 0.06 °C depending on type; checked: K at 100 °C = 4.096 mV, J at 100 °C = 5.269 mV, Pt100 at 100 °C = 138.51 Ω.
  • Copper leads at 20 °C; with 3 wires only the entered lead mismatch remains. Thermocouple extension and compensating cables are not assessed.
  • Tolerances apply to new sensors; drift from aging, contamination and transmitter error add to them.

Standards and technical documents

  • IEC 60751:2022: Industrial platinum resistance thermometers and platinum temperature sensors
  • IEC 60584-1:2013: Thermocouples — Part 1: EMF specifications and tolerances
  • NIST Monograph 175 (1993): Temperature-Electromotive Force Reference Functions and Tables for the Letter-Designated Thermocouple Types Based on the ITS-90
  • ASTM E230/E230M-23: Standard Specification for Temperature-Electromotive Force (emf) Tables for Standardized Thermocouples
  • ASTM E1137/E1137M: Standard Specification for Industrial Platinum Resistance Thermometers

U.S. regulations

  • ASME PTC 19.3-2016: Thermowells — and ASME PTC 19.3 TW-2016 for thermowell design
  • NIST Handbook 44 and ISO/IEC 17025 accreditation for calibration of temperature sensors
  • OSHA 29 CFR 1910.307: electrical equipment in hazardous (classified) locations

Frequently asked questions

How many ohms does a Pt100 read at 212 °F?

138.51 Ω per IEC 60751. At 32 °F it reads 100 Ω and at 392 °F, 175.86 Ω. Sensitivity is about 0.385 Ω/°C (0.214 Ω/°F) near freezing and falls slightly with temperature.

How many mV does a type K thermocouple produce at 212 °F?

4.096 mV with the cold junction at 32 °F. With instrument terminals at 77 °F, it measures 3.096 mV and the transmitter adds 1.000 mV of cold-junction compensation.

How much error does a 2-wire RTD have?

Each ohm of cable is worth about 2.6 °C (4.7 °F). With 150 ft of 18 AWG, both leads add about 1.92 Ω, or about 5 °C (9 °F) of error. With 3 wires, the error drops to hundredths of a degree.

What is the difference between class A and class B?

At 212 °F, class A allows ±0.35 °C (±0.63 °F) and class B ±0.80 °C (±1.44 °F). Class AA allows ±0.27 °C. Outside the validity range, treat the sensor as a wider class.