Paste the internal resistance, impedance or conductance readings of each cell to see which ones depart from baseline, which need replacing and how the string is aging.
Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.
Worsening in the latest reading (resistance or impedance increase, or conductance drop), with the warning and replacement limits.
String average and critical cells at each reading, compared with the average reference.
In order of worsening, with deviation from the reference and from the present string average.
Take this page’s results to another calculator with the fields already filled in.
The calculation report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. The full report also includes the charts and interpretations, in color. In the print dialog, choose Save as PDF.
To find weak cells before they fail in an outage, without discharging the string. Internal resistance rises as a cell loses capacity, and in a series string the weakest cell limits everyone’s run time. The calculator compares each cell with its baseline and with the others, and shows the trend across readings.
Ideally the commissioning reading, taken once the string has stabilized on float; IEEE 1188 recommends establishing a baseline. Without it, use the manufacturer value for the model, measured with the same kind of instrument, or the string average in the present reading, which highlights cells that stand out.
The example string has 16 12 V monoblocs with an average baseline of 4.20 mΩ. Cell 7 rose from 4.19 to 6.55 mΩ, 56% above baseline: past the 50% replacement limit. Cell 12 is 24% above, on watch. The others rose about 6% in three years, normal aging.
There is no single code number. Tester makers suggest investigating at 20% to 30% for VRLA and 50% to 100% for flooded cells. EPRI data show cells 50% above nominal impedance mostly have less than 80% of capacity, the replacement point in IEEE 1188 and IEEE 450. Confirm with the manufacturer and, when in doubt, run a capacity test.
They measure the same thing differently: resistance and impedance in mΩ rise with aging; conductance in siemens (mhos) falls. Values are not interchangeable between instruments. For conductance the calculator converts the limits: a 50% resistance increase equals a 33% conductance drop.
IEEE 1188 calls for quarterly internal ohmic readings on VRLA batteries; for vented batteries, at least yearly readings are common practice. Always measure at the same terminal points with the string on float. Cells on watch deserve monthly readings until the trend is clear.
It does not measure actual capacity, does not replace a discharge test and ignores temperature, float voltage and connections. A sudden jump on a single cell may just be a loose connection: retorque and measure again before replacing.
Important notice: Indus Metrics tools produce estimates and pre-sizing results from the data you enter and from published engineering methods. They do not replace design, calculations or reports signed by a licensed professional engineer (PE), nor verification against the applicable codes, standards and regulations, such as OSHA rules and the ASME codes. Material and fuel properties vary: check manufacturer data or your own process analyses before deciding. By using this site you agree to the Terms of Use.