Home / Heat & fluids

Batch tank heating and cooling time

Enter the batch, the jacket or coil area, U and the medium (steam or fluid) to find how long the product takes to reach temperature, how much heat and steam the batch uses and what it costs per batch and per year.

Pre-sizing and estimating tool: results do not replace design, calculations or reports signed by a licensed professional, nor verification against the applicable codes and standards.

Pre-sizingRevised 11/02/2026
Product in the vessel
Heat transfer
Heating or cooling medium
Losses and costs

Switching the medium loads starting temperatures and U; check them against your vessel. Fluid cost: oil or hot-water heating is usually charged per kWh of heat; tower or chilled water per kWh removed (power ÷ chiller COP) or per m³ circulated.

Your inputs stay only on this browser and are not sent anywhere. Untick to delete them.

—Batch time
—

Temperature during the batch

Product (solid line) and heating or cooling medium (dashed). The curve flattens near the end because the temperature difference shrinks.

Tap the chart to see the values.

Time versus the actual U

Same batch with U from 50% to 150% of the value entered. Shows how much the result depends on the heat transfer coefficient.

Tap the chart to see the values.

Batch tracking table

Expected product temperature, heat duty and cumulative consumption at each interval. Use it to check the real batch at the panel.

Next step

Take this page’s results to another calculator with the fields already filled in.

The calculation report gathers this page's inputs, results, equations, assumptions and references, with fields for project, engineer and revision. The full report also includes the charts and interpretations, in color. In the print dialog, choose Save as PDF.

Method, assumptions and references

Equations used

Heat capacity: C = M · cp + M_vessel · cp_vessel; U·A in W/K
Condensing steam (isothermal medium, Kern ch. 18): t = C ÷ (U·A) · ln[(Ts − Ti) ÷ (Ts − Tf)]; T(t) = Ts − (Ts − Ti) · e^(−U·A·t/C)
Fluid without phase change (Kern ch. 18): K = e^(U·A ÷ (ṁ·cp_f)); t = C ÷ (ṁ·cp_f) · K ÷ (K − 1) · ln[(Tin − Ti) ÷ (Tin − Tf)] (heating and cooling)
Fluid outlet: Tout(t) = T + (Tin − T) ÷ K; duty q = ṁ·cp_f · (1 − 1/K) · (Tin − T)
Useful heat Q = C · |Tf − Ti|; heat supplied = Q ÷ (1 − losses); steam = heat supplied ÷ h_fg(p); peak = U·A·(Ts − Ti) ÷ (1 − losses) ÷ h_fg

Assumptions and limits

  • Well-mixed product (uniform temperature), constant U, cp and flow during the batch, constant wetted area. Losses add to consumption and cost but do not lengthen the time; when cooling, heat gains from ambient are neglected.
  • Saturated steam condenses at the saturation temperature of the pressure entered (IAPWS-IF97) and leaves as saturated condensate; air or condensate held in the jacket reduce transfer and are not modeled.
  • U is the main uncertainty: typical values (Sinnott’s table of overall coefficients) vary 2 to 3 times between limits. The result is a pre-sizing estimate; for design, compute film coefficients (Bondy & Lippa) or measure on a real batch.

Standards and technical documents

  • Kern, D. Q. Process Heat Transfer. McGraw-Hill, 1950, ch. 18 (Batch and unsteady-state processes)
  • Bondy, F.; Lippa, S. Heat transfer in agitated vessels. Chemical Engineering, 90(7), Apr. 4, 1983, p. 62–71
  • Sinnott, R. K. Coulson & Richardson’s Chemical Engineering, Vol. 6: Chemical Engineering Design, 4th ed. Elsevier, 2005, ch. 12 (typical overall coefficients; jacketed vessels and coils)
  • Green, D. W.; Perry, R. H. Perry’s Chemical Engineers’ Handbook, 8th ed. McGraw-Hill, 2008, Section 11 (heat transfer in agitated vessels)
  • IAPWS-IF97: Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam

U.S. regulations

  • ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 (jacketed vessels, adopted by most U.S. states)
  • OSHA 29 CFR 1910.147: The control of hazardous energy (lockout/tagout) before opening steam jackets or vessels

Frequently asked questions

What does this calculator do?

It estimates how long a jacketed or coil-heated vessel takes to heat or cool a batch, how much heat and steam the batch uses and what that costs per batch and per year. Use it to plan the production sequence, compare steam with hot water or thermal oil, judge whether more transfer area pays off and check whether a real batch is slower than it should be.

How is heating time calculated?

With Kern’s batch equations (Process Heat Transfer, ch. 18), assuming a well-mixed product. With steam, t = C ÷ (U·A) × ln[(Ts − Ti) ÷ (Ts − Tf)], where C is mass times specific heat of the product plus the vessel. In the example, 1,300 gal of product (0.93 Btu/lb·°F) and 2,600 lb of steel heated from 77 °F to 176 °F with 45 psig steam (292 °F), U of 106 Btu/(h·ft²·°F) and 110 ft² of jacket take 33 minutes.

What changes between steam and hot water, thermal oil or cooling water?

Steam condenses at constant temperature, so only the product temperature changes. A fluid without phase change cools (or warms) as it passes through the jacket and leaves between its inlet and the product temperature; that brings in Kern’s factor K = e^(U·A ÷ ṁ·cp), and fluid flow also limits the duty. In the cooling example, taking the batch from 176 °F to 95 °F with 82 °F tower water at 22,000 lb/h and U of 62 Btu/(h·ft²·°F) takes 3 h 32 min.

Where do I get U?

The list holds midpoints from Sinnott’s table of typical overall coefficients (Coulson & Richardson, vol. 6): jacket with steam and an aqueous solution, 88 to 123 Btu/(h·ft²·°F) (500 to 700 W/m²K); steam coil in an agitated tank, 141 to 264. It is the main uncertainty: in the example, U 30% lower stretches the batch to 47 minutes and 30% higher cuts it to 25. Calibrate it: log the product temperature at two times in a real batch and adjust U until the curve matches.

How do I read steam use and peak flow?

In the example the batch uses 1,183 lb of steam including 5% losses to ambient, since each pound of 45 psig steam gives up about 916 Btu as it condenses. Flow is not constant: at the start, with cold product, it reaches 2,877 lb/h and then falls, averaging about 2,150 lb/h. Size the control valve, line, trap and boiler capacity for the peak, not the average.

What does each batch cost and how can I cut it?

With steam at $15 per 1,000 lb, the example batch costs $17.75 and 600 batches a year add up to about $10,600. To cut it: insulate the lid and shell (10% to 20% losses on a bare vessel), return condensate to the boiler, keep the jacket clean and drained (working trap and air vent) and do not heat past what the process needs, since the last degrees are the slowest.

What are the limits, and when should I call an engineer?

The calculation assumes a uniform product with constant U and cp, and ignores air or condensate held in the jacket, products that thicken and reactions that release heat. It is a pre-sizing estimate. A steam jacket is a pressure vessel under the ASME Code: working pressure, relief valve and inspections need a qualified professional, as does the design of new transfer area or an agitator.